- Water Treatment[10]
- Water Filter Parts[9]
- Water Filters[9]
- Water Filter[7]
- Other Filter Supplies[3]
- Waste Management[3]
- Contact Person : Ms. CHAN NANCY
- Company Name : Quanzhou Suoai Membrane Science & Technology Development Co., Ltd.
- Tel : 0086-595-22491007
- Fax : 0086-595-22496007
- Address : Fujian,QUAN ZHOU,3rd Floor of ZhongTai, No.26,Yushi Road,Quanzhou Economic & Technical Development Zone,
- Country/Region : China
- Zip : 362005
CENTRAL WATER FILTER SRUF-2000A WITH UF MEMBRANE
1, PERFORMANCE PARAMETERS |
|
| |
Membrane Material | PVC | ||
Molecular Weight Cut-off (MWCO) | 100.000 Daltons | ||
Inner and outer diameters of hollow-fiber | 0.9mm/1.6mm | ||
Membrane fiber type | Inside-out hollow-fiber | ||
Characteristics of membrane structure | Hydrophilic double-compact layers | ||
External Shape | Hollow fiber | ||
2, APPLICATION CONDITIONS |
| ||
Pre - filtration | 50-150 um | ||
Max turbidity of inlet water | ≤ 15 NTU | ||
Rated flux | 60 – 160 L/M/H |
| |
Running mode | Cross-flow filtration or dead end filtration | ||
Max inlet water pressure | 0.45 MPa | ||
Pressure difference of transmembrane at 20°C (TMP) | 28 – 150 KPa | ||
Max pressure difference of transmembrane | 0.2 MPa | ||
Applicable PH range | 2 – 12 | ||
Applicable temperature | 5 °C - 45 °C | ||
Tolerable continuous residual chlorine | 100 PPm | ||
Tolerable interval residual chlorine | 200 PPm | ||
3, BACKWASHING DESIGN |
| ||
Backwashing pressure | 0.25 MPa | ||
Backwashing flow | 220 – 300 L/M/H | ||
Backwashing frequency | Every 20 -60 minutes |
| |
Backwashing time | 30 – 60 seconds every time | ||
Frequency of chemically enhanced ( CEB ) | Auto adding of additives in backwashing is recommended. | ||
Time of chemically enhanced backwashing ( CEB ) | 30 – 60 seconds every time | ||
4, CHEMICALLY WASHING DESIGN |
| ||
Frequency of chemically washing | Every 1~4 months or when TMP is over 0.15 MPa | ||
Pressure of chemically washing | 0.15 MPa | ||
Flow of chemically washing | 200 – 250 L/M/H |
| |
Time of chemically washing | 60 – 90 minutes every time | ||
Acid washing chemical | Citric acid or oxalic acid ( mixed into solution with PH = 2 ) | ||
Alkali washing chemical | NaOH ( mixed into solution with PH=12) | ||
5, INDEX OF OUTPUT WATER |
| ||
Turbidity of output water | < 0.1 NTU | ||
Index of silt density | < 1.5 | ||
Microorganism, pathogen | 99.99 % Removed |
| |
Remarks: | 1. Pure water flux is measured with pure water at 25°C with inlet water pressure of 0.1MPa. | ||
| 2. If water are from surface water,river water or well water and so on,pre-treatment shall be done. It is suggested that a 50-150 um precision filter shall be equipped to have inlet water with turbidity ≤15NTU. | ||
CENTRAL WATER FILTER SRUF-2000A WITH UF MEMBRANE